CONTI+ CNX 2.0 Water management system control centre, for up to 64 faucets CONO140002
CNX 2.0 control centre
Control unit with integrated power supply for up to 64 CNX valves, with integrated web server, operable via Internet/web browser with user login.
For larger systems with more valves, a master-slave architecture can be used to expand the control system accordingly.
Data transmission via LAN and WLAN or remote access from anywhere.
The control centre is wired ready for connection and has a connection cable with a safety plug.
Suitable for wall mounting.
Generous variable line topology up to 350 m in flexible line, star or tree structure.
• Integration, management, operation, querying, adjustment and monitoring of the entire system, groups or individual fittings.
• Export function for system and status logs
• Water flow time: Adjustment option for normal operation, hygiene flushing and thermal disinfection
• Hygiene flushing: Selection, adjustment and combination options (manual, usage-dependent and calendar-dependent)
• Thermal disinfection: automatic, variable implementation in accordance with DVGW W 551, temperature logging in PDF format with optional temperature sensors
• Cold water flushing: can be activated flexibly (manually, via key switch or calendar-controlled) and individually adjustable
• Cleaning shutdown: manual, key switch or optionally via external contact
• Modular use of key switches: flexible integration into the bus and individually assignable to different action groups
• Operating and fault messages with storage in PDF format
• Power supply unit: approval according to EN 60950-1 / VDE 0805-1, EN 61000-4-2,3,4,5,6,8,11, EN 61000-3-2,-3
Consisting of:
• Plastic housing with door, RAL 7035
• CNX controller with proprietary robust BUS system, LAN connection and WLAN antenna, SD card for lifelong data backup
• Potential-free inputs for:
- Start of thermal flushing for disinfection (TD)
- Deactivation of shower operation
• Relay outputs for
- Collective fault message
- Thermal flushing successful
- Thermal flushing active
Input voltage: 230 V/AC, 50 Hz
Output voltage: 26 - 28 V/DC
Power consumption: 2 A
Power consumption (max.): 0.1 kW
Communication: 1x USB, 1x Ethernet, web server for web client
Dimensions (WxHxD): 300 x 300 x 160 mm
Protection class: I
IP protection: IP65



